Mobile menu

LW3-12 SF6 Circuit Breaker

LW3-12 SF6 HV outdoor circuit breaker is a new type product that SF6 is taken for insulating and arc extinguishing. The arc-chute consists of a breaker and an operative mechanism, using rotating arc principle. Compared with the 10KV series outdoor breakers, this kind of product has obvious advantages, such as a simple structure, the higher reliability of insulating and arc extinguishing, a lower operative power, and a higher rated parameter, a longer electrical service life, a long maintenance free duration, and so on.

This kind of product can be divided into two types: Type I and Type II. The main difference is that, type I is fitted with a kind of manual energy -storage mechanism operated by spring, mainly used on the pillar, and type II is equipped with motor-driven energy - storage mechanism operated by spring which not only can be operated by hand directly or be controlled remote, but also can do coincide automatically, mainly used in the mini-medium substation for protecting and controlling.

No

Name

Unit

Data

1

Rated voltage

KV

12

2

Rated insulating level (the pressure of SF6 in the breaker is 0.25Mpa, the temperature is 20 )

Lightning impulse withstand voltage
(full wave)

KV

75

Rated 1min power frequency withstand voltage

42

The voltage withstand test under the condition of raining

34

3

The insulating level under zero pressure
(the pressure on the highest phase is 5min)

KV

9

4

Rated current

A

400 630

5

Rated short-circuit breaking current

KA

6.3 8 12.5

6

The breaking current under  zero pressure of t

A

400 630

7

Rated short-circuit breaking times

Times

20

8

Rated operative sequence

Type I

 

Off-180s-on/off-
180s- on/off

Type II

Off -0.5s- on/off -
180s- on/off

9

Rated short-circuit breaking current (peak value)

KA

16 20 31.5

10

Rated peak withstand current (peak value)

KA

16 20 31.5

11

Rated short-time withstand time

S

4

12

Rated short-time withstand current

KA

6.3 8 12.5

13

Rated operating pressure

M Pa

0.35

14

The lowest operating pressure

M Pa

0.25

15

Annual leak rate

&

< =1

16

Mechanical Endurance

Times

2000

17

Weight

Type I

Kg

122

Type II

130

You can asking Data Sheet List for this product before order: This email address is being protected from spambots. You need JavaScript enabled to view it.or This email address is being protected from spambots. You need JavaScript enabled to view it.


Warning: count(): Parameter must be an array or an object that implements Countable in /hermes/bosnacweb05/bosnacweb05ae/b1493/dom.douglasg/public_html/mettz-us/templates/vt_findhome/html/com_k2/templates/default/item.php on line 260